Place of Origin: | China |
Brand Name: | no |
Model Number: | HLP530 |
Minimum Order Quantity: | 100pcs |
---|---|
Price: | negotiation |
Packaging Details: | carton |
Delivery Time: | 20 days after payment |
Payment Terms: | T/T |
Descriptions:
1. For use with fluorinated refrigerants as well as with a air and water.(Allowable Fluid Temp.:-10℃~+110℃)
2. Various contact functions available.
3. With SPDT contact mechanism.
4. Renovated micro-switch structure ensures the reliable switch function.
5. Manual-controlled and no use of other instruments to have a function test.
6. Flexible mounting plate suits various kinds of application.
Specifications:
Model | Range(bar) | Differential(bar) | Factory Setting(bar) | Max. Bellows Press(bar) | |||
Min | Max | Min | Max | OFF | ON | ||
HLP503 | -0.7 | 3 | 0.2 | 1.5 | 2 | 1 | 16.5 |
HLP506 | -0.7 | 6 | 0.6 | 4 | 3 | 2 | 16.5 |
HLP506M | -0.7 | 6 | Duplicate voltage disparity≤1 | 3 | Manual Reset | 16.5 | |
HLP110 | 1 | 10 | 1 | 3 | 6 | 5 | 16.5 |
HLP516 | 5 | 16 | 1 | 4 | 10 | 8 | 35 |
HLP520 | 5 | 24 | 2 | 5 | 16 | 13 | 35 |
HLP530D | 5 | 30 | 5 | 10 | 20 | 15 | 35 |
HLP530 | 8 | 30 | Fixed3-5 | 20 | 15-17 | 35 | |
HLP530M | 8 | 30 | Duplicate voltage disparity≥4 | 20 | Manual Reset | 35 |
Electric Ratings:
Rated Amps (A)Rated Voltage (V) |
Power Factor (cos) |
125/250V AC |
|
Non-Inductive Current | 1 | 12 | |
Inductive Current | Full Load | 0.75 | 12 |
Locked Rotor | 0.45 |
72 |